General monitoring information. These OIDs are deprecated, please migrate to the new ones in Section G.6.
Table G.18. iso.3.6.1.4.1.24693.1.X.Y
X.Y | Type | Meaning |
1.1 | Integer (mV) | Voltage: "A" power supply. Should be around 12V. May show a few volts when no power connected |
1.2 | Integer (mV) | Voltage: "B" power supply. Should be around 12V. May show a few volts when no power connected |
1.3 | Integer (mV) | Voltage: Combined 12V supply. Will be slightly lower than highest of "A" and "B" due to diode drop |
1.4 | Integer (mV) | Voltage: 3.3V reference |
1.5 | Integer (mV) | Voltage: 1.8V reference |
1.6 | Integer (mV) | Voltage: 1.2V reference |
1.7 | Integer (mV) | Voltage: 1.1V reference |
1.8 | Integer (mV) | Voltage: 3.3V fan power, if present |
1.9 | Integer (mV) | Voltage: 1.2V fan power, if present |
2.1 | Integer (mC) | Temperature: Fan controller |
2.2 | Integer (mC) | Temperature: CPU |
2.3 | Integer (mC) | Temperature: RTC |
3.1 | Integer (rpm) | Speed: Fan 1 |
3.2 | Integer (rpm) | Speed: Fan 2 |